+ 962 6 560 4101 sales@spectroplus.com

Valve Regulated Lead-Acid Battery Model 12V40AH

General Features

  • Thick plates and high-density active material Thick plates and high-density active material

  • High power density Low self-discharge characteristic

  • Longer life in deep cycle app locations
  • Excellent recovery from deep discharge

APPLICATION

  • Solar system
  • Wind system

Physical Specifications

Nominal Voltage 12V
Nominal Capacity (10HR ) 40AH
Dimensions Length 197±2mm
Width 166±2mm
Container height 170±2mm
Total Height (with terminal) 170±2mm
Weight±3% Approx 12.7Kg (28.00lbs)
Internal Resistance(In full charge status) ≈ 8.00mΩ
Standard Terminals F9/F36(standard)

 

Rated Capacity
10 hour rate(4.0A) 40. 0AH
20 hour rate(2.0A) 42. 0AH
120 hour rate(0.3 3A) 47. 5AH
240 hour rate(0.17A) 48. 0AH
Capacity affected by Temperature
40ºC(104ºF ) 103%
25ºC(77ºF ) 100%
0ºC(32ºF ) 86%
Cycle Application
1. Limit initial current less than 10A
2. Charge until battery voltage (under charge) reaches 14.1V to 14.4V at 25ºC(77ºF )
3. Hold at 14.1V to 14.4V until current drop to under 0.2A for at least 3 hours
4. Temperature compensation coefficient of charging voltage is -30mV/ºC
Standby Service
1. Hold battery across constant voltage source of 13.6 to 13.8 volts with current
limit 10A continuously .When held at this voltage , the battery will seek its
own current level and maintain itself in a fully charge status.
2. Temperature compensation coefficient of charging voltage is -18mV/ºC.

NOTE : The battery should be charged within 6 months of storage, Otherwise, permanent loss of capacity might occur as a result of sulfation

Battery Discharge Table

 

End
Voltage (V)
Hour (H)
1 2 4 8 10 20 48 96 120 240
Constant Current Discharge Data Sheet (Amperes at 25ºC)
10.20 22. 98 14 .22 8.73 4.83 4.00 2.06 0.941 0.493 0.410  0.210
10.50 21. 79 13 .40 8.34 4.79 3.98 2.04 0.937 0.489 0.406 0.207
10.80 20. 80 12 .59 7.93 4.76 3.96 2.02  0.925 0.485 0.403 0.206
11.10 19. 27 11.79 7.51 4.63 3.90 2.00 0.911 0.4 83 0.396 0.204
11.40 17. 97  10 .96 7.08 4.50 3.84 1.96 0.897 0.4 81 0.390 0.202
Constant Power Discharge Data Sheet (Watt at 25ºC)
10.20 238 .9 14 7.8 90. 8 50 .24 41. 59 21. 41 9.78 5.1 26 4.262 2.182
10.50 226 .5 13 9.3 86. 6 49 .83 41. 38 21. 20 9.73 5.086 4.221 2.162
10.80 216 .2 13 0.9 82. 4 49 .41 41. 18 21. 00 9.61 5.045 4.180 2.141
11.10 200 .4 12 2.5 78. 1 48 .18 40. 56 20. 80 9.4 8 5.024 4.118 2.120

 

 

 

Constant-Voltage Charge