+ 962 6 560 4101 sales@spectroplus.com

VRLA Tubular Gel Battery 2V1200Ah

OPZV SERIES

The OPZV Series use tubular gel technology, key raw material is imported from Europe, key
production equipment imported from Europe. Practice shows that the battery has superior
service life and reliability, good cycling performance and charge acceptance ability, can be
used in high-low temperature environment, poor power condition and various types of
communication base stations. This range is recommended for telecom outdoor applications,
renewable energy systems and other harsh environment applications

General Features

  • Design lfie is above 18 years in floating condition
  • Wide operating temperature range from -20℃ to 60℃
  • Tubular positive plate with prolonged cycle life
  • Nano Silica gel electrolyte
  • TECHNOLOGY PARAMETER
  • New porous PVC-SiO2 separator with low-internal resistance
  • Apply lead, calcium, tin, aluminum compound alloy
  • Low self-discharge characteristic.
  • Excellent deep discharge recovery capability
  • ABS containers and covers (UL94HB, UL94V-0) optional.

APPLICATION

  • Deep cycling energy storage application
  • Solar & wind energy storage system
  • Off-grid & bad grid hybrid sites
  • Floating applications for telecom sites

Standard

  • IEC 6089622:2004-21/IEC614272005-
  • DIN43539-T5 198
  • DIN407421999-BSEN 614272002-YD/T 13602005
  • GB/T 224732008

TECHNOLOGY PARAMETER

Battery model OPZV-1200
Normal Voltage 2V
Rated Capacity 1200Ah/10Hr 1.8V/cell @ 25 ℃(77℉)
Battery design life (Floating use) 18 Year
Dimensions Length (mm) Width (mm) Height (mm) Total Height (mm)
275 210 646 678
Approx. weight (Kgs±3%) 93 Charge current 120A (Recommendation) 300A (Maxmum)
Internal resistance (mΩ) 0.25 @ 25 ℃(77℉) Self-discharge 3% of capacity declined per month at 25℃ (average)
Recommended Operatingtemperature -20℃ ~ 25℃ (68℉~77℉ Operating Temperature Range Discharge: -20℃ ~ 50℃ (-4℉~122℉)
Charge:-20℃ ~ 50℃ (-4℉~122℉)
Storage:-5℃ ~ 40℃ (41℉~104℉)
Charge Voltage@ 25℃(77℉) Float use 2.23V/cell Temperature compensation -3mV/℃/cell
cycle use 2.352.40-V/cell Equalize 2.352.40-V/cell

Battery Discharge Table

 

End Point
Volts/Cel
Minute (M) Hour (H)
5 10 15 30 45 1 1.5 2 3 4 5 8 10 20 100 120
Constant Current Discharge Data Sheet (Amperes at 25ºC)
1.90V 1026.00 899.00 605.00 588.00 564.00 468.00 372.00 330.00 258.00 216.00 185.00 129.00 107.00 55.54 14.51 12.31
1.85V 1082.00 945.00 706.00 660.00 598.00 516.00 408.00 354.00 274.00 228.00 195.00 134.00 112.00 61.09 15.28 12.96
1.80V 1159.00 1144.00 974.00 840.00 672.00 624.00 516.00 399.00 300.00 245.00 208.00 144.00 125.00 64.14 15.81 13.41
1.75V 1206.00 1167.00 1117.00 936.00 746.00 672.00 568.00 417.00 312.00 252.00 211.00 146.00 128.00 66.70 16.21 13.74
Constant Power Discharge Data Sheet (Watt at 25ºC)
1.90V 1944.00 1685.00 812.00 740.00 707.00 674.00 637.00 600.00 493.00 417.00 359.00 261.00 225.00 111.10 29.02 24.62
1.85V 2009.00 1755.00 938.00 824.00 768.00 711.00 694.00 677.00 553.00 463.00 397.00 2 284.00 245.00 121.00 30.25 25.66
1.80V 2132.00 2103.00 1542.00 1366.00 1247.00 1128.00 976.00 823.00 656.00 537.00 455.00 320.00 274.00 125.70 30.99 26.28
1.75V 2205.00 2134.00 1776.00 1546.00 1412.00 1278.00 1086.00 894.00 694.00 568.00 475.00 326.00 276.00 128.70 31.29 26.52

 

(NOTE) The above characteristics data are average values obtained within three charge/discharge cycles not the minimum values.